Range :

Shuttle ultrasonic level transmitter is mainly used for ultrasonic level measurements in wastewater wells, sewer wells and drinking water tanks or reservoirs. Measurements are done without physical contact with the measured liquid. Furthermore, the transmitter can also be used for accurate measurements of water levels in canals and ports etc. Non-contact measurement is ideal for contaminated liquids, including aggressive chemicals or liquids with a very high concentration of dissolved solids or sludge.

Categories ,

Applications

  • Stormflow tanks
  • Pump stations
  • Tanks in sewage treatment plants
  • Tanks in water plants
  • Tanks and vessels in process and food industries.

Features

  • Multiple sensors with measuring ranges from 10 cm to 25 m.
  • Learns how the tank is arranged with piping, pumps and other items interfering with the measurement.
  • Ignores turbulence and electrical interference (even a slow moving mixer can pass through without influencing the measurement).
  • Two output relays for level/system alarm or alternating pump control with duty and standby cycles.
  • 4-20 mA output with zero and span adjustment.
  • Indicates strength of echo signal with a bar graph.
  • Narrow ultrasonic pulse signal concentrates signal strength for minimum sensitivity to foam/sludge on the liquid surface.
  • Easy to read LCD-display for both setup and indication.
  • Actual level indicated with bar graph and digits in millimeters, centimeters, meters, feet and inches.
  • Readout can be chosen as relative or absolute level.
  • 10-30 V DC or 230 V AC supply.
  • FM approved sensors for hazardous areas.

Specifications

 

Parameter Specification
Range 0-12 m, 0-15 m, 0-25 m (depending on sensor)
Span (4/20 mA) From 0-10 cm to 0-12 m/15 m/25 m
Supply Voltage 230/115 V AC ± 10% or 10-30 V DC
Power Consumption Approx. 2 W
Temperature Range -20° to +60°C
Input From ultrasonic sensor
Measurement Accuracy Better than ± 0.2%
Outputs Analog: 4 – 20 mA, max. load 500 Ω
Digital: 2 x relays with programmable NO/NC function
Max. 1 A resistive load @ 50 V
Indication LCD display with four digits and symbols
Operation Function keypad behind front panel
Enclosure IP 67
Test Approvals CE: EN 50081-1, EN 50082-1
UL: File E194021